Model:EEP-12/1600-40A
Category:Embedded poles
Specifications of Embedded Pole
Main Technical Specification | Unit | Specification | ||
1250 | 1250 | 630 | ||
Rated voltage | kV | 12 | ||
Rated current | A | 1250 | 1250 | 630 |
Rated frequency | HZ | 50/60 | ||
Short time power frequency withstand voltage(1min) | kV | 48 | ||
Lightning impulse withstand voltage | kV | 95 | ||
Rated short circuit breaking current | kA | 31.5 | 25 | 25 |
Rated peak withstand current | kA | 80 | 63 | |
Rated short circuit making current | kA | 80 | 63 | |
Rated short time withstand current | kA | 31.5 | 25 | 25 |
Rated duration of short circuit | S | 4 | ||
Rated breaking current of single capacitor bank | A | 400 | ||
Rated breaking current of back to back capacitor bank | A | 400 | ||
Rated operating sequence | O-0.3s-CO180s-CO | |||
Breaking operations of rated short circuit breaking current | Times | 30 | ||
Rated mechanical endurance | Times | 20000 | ||
Closing force due to bellow and atmosphere | N | 200±50 | ||
Force required to hold contacts open at full stroke | N | 300±50 | ||
Circuit resistance at lower limit of rated contact force | mΩ | ≤20 | ||
Contacts limit erosion | mm | 3 | ||
Gas pressure inside vacuum interrupter | Pa | ≤1x10?3 | ||
Localize discharge | Pc | ≤5 |
Mechanical Data Required for the Matched Vacuum Switchgear
Main Technical Specification | Unit | Specification | ||
1250 | 1250 | 630 | ||
Clearance between open contacts | mm | 9±1 | ||
Average opening speed | m/s | 1.2±0.2 | ||
Average closing speed | m/s | 1.0±0.2 | 0.6±0.2 | |
Rated of contact force | N | 2300±200 | 2000±200 | |
Contact bouncing duration at closing operation | ms | ≤3 | ||
Out of simultaneity of contact closing and opening | ms | ≤2 | ||
Maximum rebound during opening | mm | ≤3 |