Main Technical Parameter | ||
Rated voltage | 12kV | |
Rated current | 630/1250A | |
Rated frequency | 50Hz | |
Rated short-time Power frequency withstand voltage | 48kV | |
Rated lightning impulse withstand voltage | 85kV | |
Rated short-circuit breaking current | 25kA | |
Rated short-circuit making current(peak) | 63kA | |
Breaking operations of rated short circuit breaking current | 30 times | |
Rated breaking current of single capacitor bank | 630A | |
Rated short-time withstand current | 25kA | |
Rated peak withstand current | 63kA | |
Rated duration of short-circuit | 4 s | |
Mechanical endurance | 10000 times | |
Closing force due to bellow and atmosphere | 140±50N | |
Force required to hold contacts open at full storke | 230±50N | |
Circuit resistance at lowest rated contact force | ≤25μ? | |
Contacts limit erosion | 3mm | |
MECHANICAL DATA REQUIRED FOR THE MATCHED VACUUM SWITCHGEAR | ||
Clearance between open contacts | 11±1 mm | |
Average opening speed | 1.2±0.2m/s | |
Average closing speed | 0.6±0.2m/s | |
Rated added extemal contact final force | 2500±200N | |
Contact bouncing duration at closing operation | ≤2 ms | |
Closing and opening non-simultaneity of three-phase contacts | ≤2 mm |