Model:EEP-12/2000-40
Category:Embedded poles
Specifications of Embedded Pole
Main Technical Specification | Unit | Specification | ||
2000 | ||||
Rated voltage | kV | 12 | ||
Rated current | A | 2000 | ||
Rated frequency | HZ | 50/60 | ||
Short time power frequency withstand voltage(1min) | kV | 48 | ||
Lightning impulse withstand voltage | kV | 95 | ||
Rated short circuit breaking current | kA | 40 | 31.5 | 25 |
Rated peak withstand current | kA | 100 | 80 | 63 |
Rated short circuit making current | kA | 100 | 80 | 63 |
Rated short time withstand current | kA | 40 | 31.5 | 25 |
Rated duration of short circuit | S | 4 | ||
Rated breaking current of single capacitor bank | A | 400 | ||
Rated breaking current of back to back capacitor bank | A | 400 | ||
Rated operating sequence | O-0.3s-CO180s-CO | |||
Breaking operations of rated short circuit breaking current | Times | 30 | ||
Rated mechanical endurance | Times | 10000 | ||
Closing force due to bellow and atmosphere | N | 140±50 | ||
Force required to hold contacts open at full stroke | N | 220±50 | ||
Circuit resistance at lower limit of rated contact force | mΩ | ≤25 | ||
Contacts limit erosion | mm | 3 | ||
Gas pressure inside vacuum interrupter | Pa | ≤1x10?3 | ||
Localize discharge | Pc | ≤5 |
Mechanical Data Required for the Matched Vacuum Switchgear
Main Technical Specification | Unit | Specification | ||
2000 | ||||
Clearance between open contacts | mm | 11±1 | ||
Average opening speed | m/s | 1.05±0.15 | 1.2±0.2 | 1.2±0.2 |
Average closing speed | m/s | 0.7±0.1 | 1.0±0.2 | 0.6±0.2 |
Rated of contact force | N | 4250±250 | 2300±200 | 2000±200 |
Contact bouncing duration at closing operation | ms | ≤2 | ||
Out of simultaneity of contact closing and opening | ms | ≤2 | ||
Maximum rebound during opening | mm | ≤2 |