Model:VITF12/630-20
Category:VI for load breaking switches
Main Technical Parameter | ||
Rated voltage | 12KV | |
Rated current | 630A | |
Rated frequency | 50Hz | |
Rated short-time Power frequency withstand voltage | 42kV | |
Rated lightning impulse withstand voltage | 75kV | |
Rated short-time withstand current | 20kA | |
Rated duration of short-circuit | 4 s | |
Rated peak withstand current | 50kA | |
Rated short-circuit making current(peak) | 50kA | |
Rated active load breaking current | 630A | |
Rated closed-loop breaking current | 630A | |
Rated cable-charging breaking current | 10A | |
Rated breaking current of single capacitor bank | 400A | |
Mechanical endurance | 10000 times | |
Closing force due to bellow and atmosphere | 80±30N | |
Force required to hold contacts open at full storke | 140±40N | |
Circuit resistance at lowest rated contact force | ≤45μ? | |
Storage life | 20 years | |
Contacts limit erosion | 3mm | |
Weight of movable parts | ≤0.7kg | |
MECHANICAL DATA REQUIRED FOR THE MATCHED VACUUM SWITCHGEAR | ||
Clearance between open contacts | 9±1 mm | |
Contact connection stroke | 3±0.5mm | |
Average opening speed | 1.0±0.2m/s | |
Average closing speed | 0.6±0.2m/s | |
Rated added extemal contact final force | 900±50N | |
Contact bouncing duration at closing operation | ≤2 ms | |
Closing and opening non-simultaneity of three-phase contacts | ≤2 ms | |
Maximum rebound durning opening | ≤1.5 mm |