Model:VITD40.5/2000-31.5
Category:VI for indoor circuit breakers
Main Technical Parameter | ||
Rated voltage | 40.5KV | |
Rated current | 2000A | |
Rated frequency | 50Hz | |
Rated short-time Power frequency withstand voltage | 95kV | |
Rated lightning impulse withstand voltage | 185kV | |
Rated short-circuit breaking current | 31.5kA | |
Rated short-circuit making current(peak) | 80kA | |
Breaking operations of rated short circuit breaking current | 30 times | |
Rated breaking current of single capacitor bank | 630A | |
Rated short-time withstand current | 31.5kA | |
Rated peak withstand current | 80kA | |
Rated duration of short-circuit | 4 s | |
Mechanical endurance | 10000 times | |
Closing force due to bellow and atmosphere | 250±50N | |
Force required to hold contacts open at full storke | 330±60N | |
Circuit resistance at lowest rated contact force | ≤20μ? | |
Storage life | 20 years | |
Contacts limit erosion | 3mm | |
Weight of movable parts | ≤4kg | |
MECHANICAL DATA REQUIRED FOR THE MATCHED VACUUM SWITCHGEAR | ||
Clearance between open contacts | 22±2 mm | |
Contact connection stroke | 3.5±0.5mm | |
Average opening speed(average of 75% contact gap) | 1.8±0.25m/s | |
Average closing speed(average of last 30% contact gap) | 0.8±0.15m/s | |
Rated added extemal contact final force | 4000±200N | |
Contact bouncing duration at closing operation | ≤3 ms | |
Closing and opening non-simultaneity of three-phase contacts | ≤2 ms |